Device Functions Proline Promag 55 FOUNDATION Fieldbus
4 Block QUICK SETUP
Hauser
15
4
Block QUICK SETUP
Block
Group
Function
groups
Functions
QUICK SETUP
(B)
⇒
⇒
QS COMMISS.
⇒
T-DAT SAVE/LOAD
(1009) P. 15
Function description
QUICK SETUP
QUICK SETUP
COMMISSIONING
(1002)
Use this function to start the Setup menu for commissioning.
Options:
YES
NO
Factory setting:
NO
!
Note!
You will find a flowchart of the COMMISSIONING Setup menu on Page 16.
For more detailed information on Setup menus, please refer to the Operating Instructions
for Proline Promag 55 FOUNDATION FIELDBUS.
T-DAT SAVE/LOAD
(1009)
Use this function to save the parameter settings / configuration of the
transmitter
in a
transmitter DAT (T-DAT), or to load the parameter settings from the T-DAT into the
EEPROM (
manual
security function).
Application examples:
• After commissioning, the actual measuring point parameters can be saved to the
T-DAT as a backup.
• If the transmitter is replaced for some reason, the data from the T-DAT can be loaded
into the new transmitter (EEPROM).
Options:
CANCEL
SAVE (from EEPROM to T-DAT)
LOAD (from the T-DAT into EEPROM)
Factory setting:
CANCEL
!
Note!
• If the target device has an older software version, the message "TRANSM. SW-DAT" is
displayed during startup. Then only the SAVE option is available.
• LOAD
This option is only possible if:
– The target device has the same software version as, or a more recent software
version than, the source device or
– The T-DAT contains valid data that can be retrieved
• SAVE