Device functions Proline Promag 55 FOUNDATION Fieldbus
3 Transducer Block
Hauser
93
Sys. -
T-DAT Save/Load
AUTO - OOS
Use this parameter to save the parameter settings/configuration of the
transmitter
in a transmitter DAT (T-DAT), or to load the parameter
settings from the T-DAT into the EEPROM (
manual
backup function).
Application examples:
• After commissioning, the actual measuring point parameters can be
saved to the
T-DAT as a backup.
• If the transmitter is replaced for some reason, the data from the T-DAT
can be loaded into the new transmitter (EEPROM).
Options:
CANCEL
SAVE (from EEPROM to T-DAT)
LOAD (from the T-DAT into EEPROM)
Factory setting:
CANCEL
!
Note!
• If the target device has an older software version, the message
"TRANSM. SW-DAT" is displayed during startup. Then only the SAVE
option is available.
• LOAD
This option is only possible if:
– The target device has the same software version as, or a more recent
software version than, the source device or
– The T-DAT contains valid data that can be retrieved
• SAVE
This option is always available.
"Diagnosis" Transducer Block/base index 1600
Parameter
Write access with
operating mode
(MODE_BLK)
Description