74
Reference Manual
00809-0100-2240, Rev DA
October 2017
XD_SCALE and OUT_SCALE
The XD_SCALE and OUT_SCALE each include three parameters: 0%, 100%, and engineering units. Set
these based on the L_TYPE:
L_TYPE is Direct
When the desired output is the measured variable, set the XD_SCALE to represent the operating range of
the process. Set OUT_SCALE to match XD_SCALE.
L_TYPE is Indirect
When an inferred measurement is made based on the sensor measurement, set the XD_SCALE to
represent the operating range that the sensor will see in the process. Determine the inferred
measurement values that correspond to the XD_SCALE 0 and 100% points and set these for the
OUT_SCALE.
L_TYPE is Indirect Square Root
When an inferred measurement is made based on the transmitter measurement and the relationship
between the inferred measurement and sensor measurement is square root, set the XD_SCALE to
represent the operating range that the sensor will see in the process. Determine the inferred
measurement values that correspond to the XD_SCALE 0 and 100% points and set these for the
OUT_SCALE.
Engineering units
Note
To avoid configuration errors, only select Engineering Units for XD_SCALE and OUT_SCALE that are
supported by the device (see
Summary of Contents for Rosemount 2240S
Page 2: ......
Page 10: ...viii Reference Manual 00809 0100 2240 Rev DA Title Page October 2017 Title Page ...
Page 16: ...6 Reference Manual 00809 0100 2240 Rev DA Introduction October 2017 Introduction ...
Page 28: ...18 Reference Manual 00809 0100 2240 Rev DA Overview October 2017 Overview ...
Page 192: ...182 Reference Manual 00809 0100 2240 Rev DA Index October 2017 Index ...
Page 193: ......