To connect the sensor wires for a temperature detector to a Rosemount 2240S do the following:
1. Make sure the power supply is switched off.
2. Loosen the four screws and remove the cover from the terminal compartment.
3. Run the wires for temperature elements and water level sensor through the sleeve at the bottom of
the transmitter housing, see
If the 2240S transmitter is mounted on a wall or pipe (remote mounting), run the sensor wires
through the appropriate cable gland/conduit entry, see
4. Connect the
temperature sensor
wires to the terminals marked “1” to “16” and “a”, “b”, “c”, and
depending on the sensor type and
measurement method that is used.
5. Connect the red, green, white, and black
water level sensor
wires to the
Sensorbus
terminal as
shown in
.
6. Connect the shield on the water level sensor cable to one of the ground terminals.
7. Make sure the cover sealing is placed in the correct position.
8. Attach the cover on the terminal compartment and tighten the four screws.
9. Tighten the cable glands.
Figure 4-8. Terminal for Connection of Temperature Elements
A.Internal grounding terminals
B. Cable entries
C. Cable entry for integrated MST/WLS sensor
D. RTD channel numbers ( 1 .. 16)
E. Sensorbus terminal
F. Wire color: Red (+), Green (B), White (A), Black (-)
A
C
B
D
E
F
Summary of Contents for Rosemount 2240S
Page 2: ......
Page 10: ...viii Reference Manual 00809 0100 2240 Rev DA Title Page October 2017 Title Page ...
Page 16: ...6 Reference Manual 00809 0100 2240 Rev DA Introduction October 2017 Introduction ...
Page 28: ...18 Reference Manual 00809 0100 2240 Rev DA Overview October 2017 Overview ...
Page 192: ...182 Reference Manual 00809 0100 2240 Rev DA Index October 2017 Index ...
Page 193: ......