162
October 2017
Reference Manual
00809-0100-2240, Rev DA
Table C-3. Analog Input Function Block System Parameters
Parameter
Index
Number
Units
Description
ACK_OPTION
23
None
Used to set auto acknowledgment of alarms.
ALARM_HYS
24
Percent
The amount the alarm value must return within the alarm limit
before the associated active alarm condition clears.
ALARM_SEL
38
None
Used to select the process alarm conditions that will cause the
OUT_D parameter to be set.
ALARM_SUM
22
None
The summary alarm is used for all process alarms in the block.
The cause of the alarm is entered in the subcode field. The first
alarm to become active will set the Active status in the Status
parameter. As soon as the Unreported status is cleared by the
alarm reporting task, another block alarm may be reported
without clearing the Active status, if the subcode has changed.
ALERT_KEY
04
None
The identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.
BLOCK_ALM
21
None
The block alarm is used for all configuration, hardware,
connection failure or system problems in the block. The cause of
the alarm is entered in the subcode field. The first alarm to
become active will set the Active status in the Status parameter.
As soon as the Unreported status is cleared by the alarm
reporting task, another block alarm may be reported without
clearing the Active status, if the subcode has changed.
BLOCK_ERR
06
None
This parameter reflects the error status associated with the
hardware or software components associated with a block. It is a
bit string, so that multiple errors may be shown.
CHANNEL
15
None
The CHANNEL value is used to select the measurement value.
Refer to the appropriate device manual for information about
the specific channels available in each device.
You must configure the CHANNEL parameter before you can
configure the XD_SCALE parameter. See
.
FIELD_VAL
19
Percent
The value and status from the transducer block or from the
simulated input when simulation is enabled.
GRANT_DENY
12
None
Options for controlling access of host computers and local
control panels to operating, tuning, and alarm parameters of
the block. Not used by device.
HI_ALM
34
None
The HI alarm data, which includes a value of the alarm, a
timestamp of occurrence and the state of the alarm.
HI_HI_ALM
33
None
The HI HI alarm data, which includes a value of the alarm, a
timestamp of occurrence and the state of the alarm.
HI_HI_LIM
26
EU of
PV_SCALE
The setting for the alarm limit used to detect the HI HI alarm
condition.
HI_HI_PRI
25
None
The priority of the HI HI alarm.
HI_LIM
28
EU of
PV_SCALE
The setting for the alarm limit used to detect the HI alarm
condition.
HI_PRI
27
None
The priority of the HI alarm.
IO_OPTS
13
None
Allows the selection of input/output options used to alter the
PV. Low cutoff enabled is the only selectable option.
L_TYPE
16
None
Linearization type. Determines whether the field value is used
directly (Direct) or is converted linearly (Indirect).
Summary of Contents for Rosemount 2240S
Page 2: ......
Page 10: ...viii Reference Manual 00809 0100 2240 Rev DA Title Page October 2017 Title Page ...
Page 16: ...6 Reference Manual 00809 0100 2240 Rev DA Introduction October 2017 Introduction ...
Page 28: ...18 Reference Manual 00809 0100 2240 Rev DA Overview October 2017 Overview ...
Page 192: ...182 Reference Manual 00809 0100 2240 Rev DA Index October 2017 Index ...
Page 193: ......