Configuration examples
Configuration of the water level sensor can basically be divided into three different cases as illustrated in
below.
X<0
: Water Zero Level is located below the Tank Zero Level.
X=0
: Water Zero Level is located at the same position as the Tank Zero Level.
X>0
: Water Zero Level is located above the Tank Zero Level.
Table 5-2. WLS Configuration
LSL=Lower Sensor Limit
USL=Upper Sensor Limit
L
A
=Active Length
Water Zero Level (0%) is below Tank
Zero Level
:
X<0
Example:
L
A
=500 mm,
X
= -50 mm.
LSL (0%)= -50 mm.
USL(100%) = 500 + (-50)=450 mm.
Water Zero Level (0%) is equal to Tank
Zero Level
:
X=0
Example:
L
A
=500 mm,
X
=0 mm.
LSL (0%) = 0 mm.
USL (100%) = 500 mm.
Water Zero Level (0%) is above Tank
Zero Level
:
X>0
Example:
L
A
=500 mm,
X
=70 mm.
LSL (0%) = 70 mm.
USL (100%)= 500 + 70=570 mm.
Tank Zero
Level
Water Zero
Level
X<0
100%
0%
Tank Zero
Level
100%
0%
Water Zero
Level
X=0
Water Zero
Level
X>0
Tank Zero
Level
100%
0%