SP
EU of PV_SCALE
The target block output value (set point).
SP_HI_LIM
EU of PV_SCALE
The highest set point value allowed.
SP_LO_LIM
EU of PV_SCALE
The lowest set point value allowed.
SP_RATE_DN
EU of PV_SCALE
per second
Ramp rate for downward set point changes. When the ramp rate is set
to zero, the set point is used immediately.
SP_RATE_UP
EU of PV_SCALE
per second
Ramp rate for upward set point changes. When the ramp rate is set to
zero, the set point is used immediately.
SP_WRK
EU of PV_SCALE
The working set point of the block. It is the result of set point
rate-of-change limiting. The value is converted to percent to obtain
the block’s OUT value.
Parameter
Units
Description