104
Reference Manual
00809-0100-2240, Rev DA
October 2017
5.16.1
Alert default settings
The following default settings are used for the Rosemount 2240S Multi-input Temperature Transmitter.
You may configure error types in a different way if you like. For example, the Temperature Measurement
Failure error is disabled by default. The Alert Setup window allows you to enable the alert as Failure, Out of
Specification, Maintenance Required, or Function Check instead.
Multi-input temperature transmitter
Table 5-18. Default Alert Configuration for Multi-input Temperature Transmitter
FF I/O board
Table 5-19. Default Alert Configuration for FF I/O Board
Error type
Default configuration
Enabled /
Disabled
Average Temperature Measurement Failure
NA
Disabled
Configuration Error
Out of Specification
Enabled
Database error
Failure
Enabled
Internal Temperature Out of Limits
Out of Specification
Enabled
Invalid Model Code
Out of Specification
Enabled
Software failure
Failure
Enabled
Temperature Measurement Failure
NA
Disabled
Error type
Default configuration
Enabled /
Disabled
Check function
Function Check
Enabled
Electronics failure - FF I/O Board
Failure
Enabled
Electronics failure - Main Board
Failure
Enabled
Internal communication failure
Failure
Enabled
Memory failure FF I/O Board
Failure
Enabled
Summary of Contents for Rosemount 2240S
Page 2: ......
Page 10: ...viii Reference Manual 00809 0100 2240 Rev DA Title Page October 2017 Title Page ...
Page 16: ...6 Reference Manual 00809 0100 2240 Rev DA Introduction October 2017 Introduction ...
Page 28: ...18 Reference Manual 00809 0100 2240 Rev DA Overview October 2017 Overview ...
Page 192: ...182 Reference Manual 00809 0100 2240 Rev DA Index October 2017 Index ...
Page 193: ......