5.10.2
Factory supplied AI blocks
The Rosemount 2240S is supplied with six pre-configured AI blocks according to
configuration can be changed if needed.
Table 5-10. Factory Supplied AI Blocks
5.10.3
Modes
The AI Function Block supports three modes of operation as defined by the MODE_BLK parameter:
Manual (Man) The block output (OUT) may be set manually
Automatic (Auto) OUT reflects the analog input measurement or the simulated value when simulation
is enabled
Out of Service (O/S) The block is not processed. FIELD_VAL and PV are not updated and the OUT status
is set to Bad: Out of Service. The BLOCK_ERR parameter shows Out of Service. In this mode, you can
make changes to all configurable parameters. The target mode of a block may be restricted to one or
more of the supported modes.
AI Block
Channel
L-Type
Units
1
CHANNEL_ TEMP_AVERAGE_LIQUID
Direct
deg C
2
CHANNEL_ TEMP_AVERAGE_VAPOR
Direct
deg C
3
CHANNEL_ TANK_TEMPERATURE
Direct
deg C
4
CHANNEL_WATER_LEVEL
Direct
meter
5
CHANNEL_HOUSING_TEMPERATURE
Direct
deg C
6
CHANNEL_PRESSURE
Direct
bar