124
Reference Manual
00809-0100-2240, Rev DA
October 2017
6.3.3
Device errors
shows a list of error messages for the Rosemount 2240S Multi-input Temperature Transmitter.
The error messages may appear on the display of a Rosemount 2410 Tank Hub and in the Rosemount
Tankmaster program.
Detailed information about the different error messages can be found in Input registers 1100 to 1134 as
shown in
“Viewing input and holding registers” on page 108
for more information on how
to view Input Registers.
Table 6-6. Device errors for the Rosemount 2240S Multi-input Temperature Transmitter
Message
Description
Action
RAM error
Input register no. 1100
(1)
.
Bit 0: RAM
The message indicates a serious working
memory problem.
1.
The register number refers to the internal Input Register in the Rosemount 2240S database.
Contact Emerson Automation
Solutions/Rosemount TankGauging
service department.
FPROM error
Input register no. 1102. The message
indicates a serious FPROM error.
Bit 0: Checksum error
Bit 4: Boot checksum
Bit 5: Boot version
Bit 6: Application checksum
Bit 7: Application version
Hreg error
Input register no. 1104.
Bit 0: Checksum error
Bit 1: Limit error, out of range
Bit 2: Software version error
Bit 3: HREG read error
Bit 4: HREG write error
SW error
Input register no. 1106.
Bit 0: Undefined software error
Bit 1: Task not running
Bit 2: Out of stack space
Bit 3: Unused RAM access
Bit 4: Divide by zero error
Bit 5: Reset counter overflow
Bit 15: Simulated SW error
Other memory
error
Input register no. 1108.
Bit 0: NVRAM access
ITemp error
Input register no. 1118. Internal
temperature error.
Bit 0: Internal temperature out of range
Bit 1: Communication error with
temperature chip
Bit 2: Temperature device error
Measurement
error
Input register no. 1122.
Bit 0: A/D communication error
Bit 1: Reference resistor error
Bit 2: Power supply error
Bit 3: A/D time-out
•
Check power supply
•
Contact Emerson Automation
Solutions/Rosemount TankGauging
service department.
Configuration
error
Input register no. 1124.
Bit 1: Unit not Supported
Choose a supported measurement unit
and reset the Rosemount 2240S
transmitter
numHidden errors
Input register no. 1132.
Number of hidden errors
Contact Emerson Automation
Solutions/Rosemount TankGauging
service department.
numOther errors
Input register no. 1134.
Number of other errors.
Summary of Contents for Rosemount 2240S
Page 2: ......
Page 10: ...viii Reference Manual 00809 0100 2240 Rev DA Title Page October 2017 Title Page ...
Page 16: ...6 Reference Manual 00809 0100 2240 Rev DA Introduction October 2017 Introduction ...
Page 28: ...18 Reference Manual 00809 0100 2240 Rev DA Overview October 2017 Overview ...
Page 192: ...182 Reference Manual 00809 0100 2240 Rev DA Index October 2017 Index ...
Page 193: ......