3.5
Installing a temperature sensor tube
Follow these steps to install the temperature sensor tube:
1. Mount the anchor weight on the tube.
2. Mount the tube so that the threads at the top of the tube fits the nozzle flange as illustrated in
:
Figure 3-5. Adjusting the temperature sensor tube
3. When the tube is placed on the nozzle, adjust the vertical position with the lock nuts. If a weight is
placed at the end of the tube, it should barely touch the tank bottom.
4. Install the Rosemount 2240S Multi-Input Temperature Transmitter, see
.
Note
Ensure that the flexible protection tube is in a vertical position to obtain correct measurement data.
Lock nut
Tube
Anchor
weight
Threads
Lock nut
2.5-15 kg
(5.5-33 lbs)
85-330 mm
(33-130 in.)