Service Mode / Parameter Level
- 38 -
11.6.1
Position Reached
The output signal is wiping when a time is entered or static when zero is set.
It is set when the positioning of the corresponding axis is completed.
11.6.2
Spindle Compensation
At the peak of the loop run, the drive signals drop off. Only after this time has elapsed, the controller returns to
the target value (adjustment range 0.1 sec … 99.9 sec).
11.6.3
Manual Change
After this time has elapsed, the system switches from a low speed to a higher speed in manual mode.
11.6.4
Monitoring
A time (0.1 ... 99.9 sec.) for encoder monitoring can be set here. If no more encoder signals are detected for
the duration of the time set here, the drive signals are switched off to stop the motor.
11.6.5
Delay Contr. Start
With a start command, the start of positioning is delayed by this time.
11.6.6
Delay Contr. Inpos.
After a position is reached, the output signal is delayed by this time entered in X.X sec.
11.6.7
Start Delay
With a start command, the start of positioning is delayed by this time.
11.6.8
Shutdown Contr.
Here the time in X.X sec. is entered for shutdown after the position is reached.
11.6.9
Retract Time
Here the time in X.X sec. is entered, after which is positioned from the retract peak back to the target value.
11.6.10
Turning Back Reference Time
In the peak of the reference run, the drive signals drop off. The positioning is only continued after this time has
elapsed (setting range 0.1 … 99.9 sec).
Summary of Contents for P40T-002 Series
Page 49: ...Service Mode Parameter Level 49 11 11Sub Menu Times System Figure 33 System Times ...
Page 83: ... 83 Notes ...
Page 84: ... 84 Notes ...
Page 85: ... 85 Notes ...