EDR-3000
IM02602003E
Parameter
Description
Setting range
Default
Menu path
t-Lock2Ready
This timer is started by the lockout reset signal, and
before the timer expire the AR cannot go to any other
state.
0.01 - 9999.00s
10.0s
[Protection Para
/<1..4>
/AR
/General Settings]
t-Run2Ready
Examination Time: If the Breaker remains after an
reclosure attempt (shot) for the duration of this timer in
the Closed position, the AR has been successful and the
AR module returns into the ready state.
0.01 - 9999.00s
10.0s
[Protection Para
/<1..4>
/AR
/General Settings]
t-Block2Ready
The release (de-blocking) of the AR will be delayed for
this time, if there is no blocking signal anymore.
0.01 - 9999.00s
10.0s
[Protection Para
/<1..4>
/AR
/General Settings]
t-AR Supervision
AR Overall supervision time (> sum of all the timers used
by AR)
1.00 - 9999.00s
100.0s
[Protection Para
/<1..4>
/AR
/General Settings]
Service Alarm 1
As soon as the AR-Counter exceeds this number of
reclosure attempts, an alarm will be given out
(overhauling of the Bkr)
1 - 65535
1000
[Protection Para
/<1..4>
/AR
/AR Wear Superv]
Service Alarm 2
Too many auto reclosure attempts. If the parameterized
number of AR cycles is reached, an alarm will be given
out.
1 - 65535
65535
[Protection Para
/<1..4>
/AR
/AR Wear Superv]
Max AR/h
Maximum Number of permitted Autoreclosure Cycles per
hour.
1 - 20
10
[Protection Para
/<1..4>
/AR
/AR Wear Superv]
Initiate AR:
InitiateFc1
Initiate Auto Reclosure : Initiate Function
Start fct
-.-
[Protection Para
/<1..4>
/AR
/Shot Manager
/Initiate AR]