EDR-3000
IM02602003E
Device Planning Parameters of the Failure Simulator
Parameter
Description
Options
Default
Menu path
Mode
Mode
Do not use,
Use
Use
[Device Planning]
Global Protection Parameter of the Failure Simulator
Parameter
Description
Setting range
Default
Menu path
PreFault
Pre Fault Duration
0.00 - 300.00s
0.0s
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/Times]
FaultSimulation
Duration of Fault Simulation
0.00 - 10800.00s
0.0s
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/Times]
PostFault
PostFault
0.00 - 300.00s
0.0s
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/Times]
TripCmd Mode
Trip Command Mode
No TripCmd,
With TripCmd
No TripCmd
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Process]