EDR-3000
IM02602003E
Parameter
Description
Setting range
Default
Menu path
Debouncing Time 5 A change of the state of a digital input will only be
recognized after the debouncing time has expired
(become effective). Thus, transient signals will not be
misinterpreted.
No Debouncing
Time,
20 ms,
50 ms,
100 ms
20 ms
[Device Para
/Digital Inputs
/DI-8P X1
/Group 3]
Inverting 6
Inverting the input signals.
Inactive,
Active
Inactive
[Device Para
/Digital Inputs
/DI-8P X1
/Group 3]
Debouncing Time 6 A change of the state of a digital input will only be
recognized after the debouncing time has expired
(become effective). Thus, transient signals will not be
misinterpreted.
No Debouncing
Time,
20 ms,
50 ms,
100 ms
20 ms
[Device Para
/Digital Inputs
/DI-8P X1
/Group 3]
Inverting 7
Inverting the input signals.
Inactive,
Active
Inactive
[Device Para
/Digital Inputs
/DI-8P X1
/Group 3]
Debouncing Time 7 A change of the state of a digital input will only be
recognized after the debouncing time has expired
(become effective). Thus, transient signals will not be
misinterpreted.
No Debouncing
Time,
20 ms,
50 ms,
100 ms
20 ms
[Device Para
/Digital Inputs
/DI-8P X1
/Group 3]
Inverting 8
Inverting the input signals.
Inactive,
Active
Inactive
[Device Para
/Digital Inputs
/DI-8P X1
/Group 3]
Debouncing Time 8 A change of the state of a digital input will only be
recognized after the debouncing time has expired
(become effective). Thus, transient signals will not be
misinterpreted. 8
No Debouncing
Time,
20 ms,
50 ms,
100 ms
20 ms
[Device Para
/Digital Inputs
/DI-8P X1
/Group 3]
www.eaton.com
66