EDR-3000
IM02602003E
SOTF - Switch Onto Fault Protection
SOTF
In case a faulty line is energized (e.g.: when an grounding switch is in the CLOSE position), an instantaneous trip is
required. The SOTF module is provided to generate a permissive signal for other protection functions such as
overcurrents to accelerate their trips. The SOTF condition is recognized according to the User’s operation mode that
can be based on:
The breaker state;
No current flowing;
Breaker state and no current flowing;
Breaker switched on manually; and/or
An external trigger.
This protection module can initiate a high speed trip of the overcurrent protection modules. The module can be started
via a digital input that indicates that the breaker is manually closed.
This module issues a signal only (the module is not armed and does not
issue a trip command).
In order to influence the trip settings of the overcurrent protection in case
of switching onto a fault, the User has to assign the signal “SOTF
.
ENABLED
“
to an Adaptive Parameter Set. Please refer to Parameter / Adaptive
Parameter Sets sections. Within the Adaptive Parameter Set, the User has
to modify the trip characteristic of the overcurrent protection according to
the User's needs.
www.eaton.com
493
Summary of Contents for EDR 3000
Page 2: ......
Page 4: ......
Page 6: ......
Page 7: ...Medium Voltage Switchgear Assembly...
Page 8: ......
Page 10: ......
Page 11: ...Component Data...
Page 12: ......