EDR-3000
IM02602003E
Parameter
Description
Setting range
Default
Menu path
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/ZI
/General Settings]
Blo TripCmd
Permanent blocking of the Trip Command of the
module/element.
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/ZI
/General Settings]
ExBlo TripCmd Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/ZI
/General Settings]
ZI OUT Fc
Zone Interlocking Out activate (allow) / inactivate
(disallow)
Inactive,
Active
Active
[Protection Para
/<1..4>
/ZI
/Zone Out]
Fault Type
Fault Type
Phase,
Ground,
Both
Both
[Protection Para
/<1..4>
/ZI
/Zone Out]
Trip
Signal: Zone Interlocking Trip
Inactive,
Active
Active
[Protection Para
/<1..4>
/ZI
/Zone Trip]
Fault Type
Fault Type
Phase,
Ground,
Both
Both
[Protection Para
/<1..4>
/ZI
/Zone Trip]
www.eaton.com
463