Device Planning Parameters of the Cold Load Pickup Module
Parameter
Description
Options
Default
Menu path
Mode
Mode
Do not use,
Use
Use
[Device Planning]
Global Protection Parameter of the Cold Load Pickup Module
Parameter
Description
Setting range
Default
Menu path
Mode
Mode
Bkr State,
I<,
Bkr State Or I<,
Bkr State And I<
Bkr State
[Protection Para
/Global Prot Para
/CLPU]
ExBlo1
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/CLPU]
ExBlo2
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/CLPU]
Rvs Blo
Reverse Blocking, if Reverse Blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/CLPU]
www.eaton.com
488