EDR-3000
IM02602003E
Global Protection Parameters of the Switch Onto Fault Module
Parameter
Description
Setting range
Default
Menu path
Mode
Mode
Bkr State,
I<,
Bkr State And I<,
Bkr manual CLOSE,
Ext SOTF
Bkr manual
CLOSE
[Protection Para
/Global Prot Para
/SOTF]
ExBlo1
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/SOTF]
ExBlo2
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/SOTF]
Rvs Blo
Reverse Blocking, if Reverse Blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/SOTF]
Ext SOTF
External Switch Onto Fault
Only available if: Mode = Ext SOTF
1..n, DI-LogicList
-.-
[Protection Para
/Global Prot Para
/SOTF]
www.eaton.com
496