EDR-3000
IM02602003E
Parameter
Description
Setting range
Default
Menu path
Pickup (sensitive)
If the pickup value is exceeded, the module/element will
be started.
0.002 - 2.000In
0.02In
[Protection Para
/<1..4>
/I-Prot
/50X[1]]
t
Tripping delay
Only available if: Characteristic = DEFT
0.00 - 300.00s
0.5s
[Protection Para
/<1..4>
/I-Prot
/50X[1]]
www.eaton.com