EDR-3000
IM02602003E
Device Parameters of RO-5 X
Parameter
Description
Setting range
Default
Menu path
Operating Mode
Operating Mode
Norm De-energ,
Norm Energ
Norm De-energ
[Device Para
/Relay Outputs
/RO-5 X2
/RO 1]
t-Off Delay
Switch Off Delay
0.00 - 300.00s
0.2s
[Device Para
/Relay Outputs
/RO-5 X2
/RO 1]
Latched
Defines whether the Relay Output will be latched when it
picks up.
Inactive,
Active
Inactive
[Device Para
/Relay Outputs
/RO-5 X2
/RO 1]
Acknowledgment
Acknowledgment Signal - An acknowledgment signal
(that acknowledges the corresponding Relay Output) can
be assigned to each Relay Output. The
acknowledgement-signal is only effective if the parameter
"Latched" is set to active.
Only available if: Latched = Active
1..n, Assignment
List
-.-
[Device Para
/Relay Outputs
/RO-5 X2
/RO 1]
Assignment 1
Assignment
1..n, Assignment
List
Bkr.TripCmd
[Device Para
/Relay Outputs
/RO-5 X2
/RO 1]
Inverting 1
Inverting of the state of the assigned signal.
Inactive,
Active
Inactive
[Device Para
/Relay Outputs
/RO-5 X2
/RO 1]
Assignment 2
Assignment
1..n, Assignment
List
-.-
[Device Para
/Relay Outputs
/RO-5 X2
/RO 1]
Inverting 2
Inverting of the state of the assigned signal.
Inactive,
Active
Inactive
[Device Para
/Relay Outputs
/RO-5 X2
/RO 1]
www.eaton.com
93
Summary of Contents for EDR 3000
Page 2: ......
Page 4: ......
Page 6: ......
Page 7: ...Medium Voltage Switchgear Assembly...
Page 8: ......
Page 10: ......
Page 11: ...Component Data...
Page 12: ......