EDR-3000
IM02602003E
•
After the
»t load Off« timer has expired, the signal ”CPLU.E
NABLED
“=1 has to become true.
•
Write down the measured time.
Successful test result:
The measured total tripping delays or individual tripping delays, threshold values, and drop-out ratios correspond with
those values specified in the adjustment list. Permissible deviations/tolerances can be found in the Technical Data sec-
tion.
www.eaton.com
492