EDR-3000
IM02602003E
Name
Description
Assignment via
SC CLOSE-I
State of the module input: Switching CLOSE Command, e.g. the
state of the Logics or the state of the digital input
[Control
/Bkr
/Ex OPEN/CLOSE Cmd]
SC OPEN-I
State of the module input: Switching OPEN Command, e.g. the
state of the Logics or the state of the digital input
[Control
/Bkr
/Ex OPEN/CLOSE Cmd]
Switchgear/Breaker Signals (Output States)
Signal
Description
SI SingleContactInd
Signal: The Position of the Switchgear is detected by one auxiliary contact (pole) only. Thus
indeterminate and disturbed Positions cannot be detected.
Pos not CLOSE
Signal: Pos not CLOSE
Pos CLOSE
Signal: Breaker is in CLOSE-Position
Pos OPEN
Signal: Breaker is in OPEN-Position
Pos Indeterm
Signal: Breaker is in Indeterminate Position
Pos Disturb
Signal: Breaker Disturbed - Undefined Breaker Position. The feed-back signals (Position
Indicators) contradict themselves. After expiring of a supervision timer this signal becomes true.
State
Signal: Breaker Position (0 = Indeterminate, 1 = OPEN, 2 = CLOSE, 3 = Disturbed)
Ready
Signal: Breaker is ready for operation.
Interl CLOSE
Signal: One or more IL_Close inputs are active.
Interl OPEN
Signal: One or more IL_Open inputs are active.
CES succesf
Signal: Command Execution Supervision: Switching command executed successfully.
CES Disturbed
Signal: Command Execution Supervision: Switching Command unsuccessful. Switchgear in
disturbed position.
CES Fail TripCmd
Signal: Command Execution Supervision: Command execution failed because trip command is
pending.
CES SwitchgDir
Signal: Command Execution Supervision respectivly Switching Direction Control: This signal
becomes true, if a switch command is issued even though the switchgear is already in the
requested position. Example: A switchgear that is already OPEN should be switched OPEN again
(doubly). The same applies to CLOSE commands.
CES CLOSE d OPEN
Signal: Command Execution Supervision: CLOSE Command during a pending OPEN Command.
CES SG not ready
Signal: Command Execution Supervision: Switchgear not ready
CES Field Interl
Signal: Command Execution Supervision: Switching Command not executed because of field
interlocking.
CES SyncTimeout
Signal: Command Execution Supervision: Switching Command not executed. No Synchronization
signal while t-sync was running.
CES SG removed
Signal: Command Execution Supervision: Switching Command unsuccessful, Switchgear
removed.
Prot CLOSE
Signal: CLOSE command issued by the Prot module