EDR-3000
IM02602003E
Direct Commands of the IEC 61850
Parameter
Description
Setting range
Default
Menu path
ResetStatistic
Reset of all IEC61850 diagnostic counters
Inactive,
Active
Inactive
[Operation
/Reset]
Global Protection Parameters of the IEC 61850
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Device Para
/IEC61850]
VirtualOutput1
Virtual Output. This signal can be assigned or visualized
via the SCD file to other devices within the IEC61850
substation.
1..n, Assignment
List
-.-
[Device Para
/IEC61850]
VirtualOutput2
Virtual Output. This signal can be assigned or visualized
via the SCD file to other devices within the IEC61850
substation.
1..n, Assignment
List
-.-
[Device Para
/IEC61850]
VirtualOutput3
Virtual Output. This signal can be assigned or visualized
via the SCD file to other devices within the IEC61850
substation.
1..n, Assignment
List
-.-
[Device Para
/IEC61850]
VirtualOutput4
Virtual Output. This signal can be assigned or visualized
via the SCD file to other devices within the IEC61850
substation.
1..n, Assignment
List
-.-
[Device Para
/IEC61850]
VirtualOutput5
Virtual Output. This signal can be assigned or visualized
via the SCD file to other devices within the IEC61850
substation.
1..n, Assignment
List
-.-
[Device Para
/IEC61850]
VirtualOutput6
Virtual Output. This signal can be assigned or visualized
via the SCD file to other devices within the IEC61850
substation.
1..n, Assignment
List
-.-
[Device Para
/IEC61850]
www.eaton.com
280