Global Protection Parameters of the Breaker Wear Module
Parameter
Description
Setting range
Default
Menu path
Operations Alarm
Service Alarm, too many Operations
1 - 100000
9999
[Control
/Bkr
/Bwear]
Isum Intr Alarm
Alarm, the Sum (Limit) of interrupting currents has been
exceeded.
0.00 - 2000.00kA
100.00kA
[Control
/Bkr
/Bwear]
Isum Intr ph Alm
Alarm, the per hour Sum (Limit) of interrupting currents
has been exceeded.
0.00 - 2000.00kA
100.00kA
[Control
/Bkr
/Bwear]
Bwear Curve Fc
The Breaker Wear Curve defines the maximum allowed
CLOSE/OPEN cycles depending on the brake currents. If
the breaker maintenance curve is exceeded, an alarm
will be issued. The breaker maintenance curve is to be
taken from the technical data sheet of the breaker
manufactor. By means of the available points this curve
is to be replicated.
Inactive,
Active
Inactive
[Control
/Bkr
/Bwear]
WearLevel Alarm
Breaker Wear curve Alarm
Only available if:Bwear Curve Fc = Active
0.00 - 100.00%
80.00%
[Control
/Bkr
/Bwear]
WearLevel Lockout Breaker Wear Curve Lockout Level
Only available if:Bwear Curve Fc = Active
0.00 - 100.00%
95.00%
[Control
/Bkr
/Bwear]
Current1
Interrupted Current Level #1
Only available if:Bwear Curve Fc = Active
0.00 - 2000.00kA
0.1kA
[Control
/Bkr
/Bwear]
Count1
Open Counts Allowed #1
Only available if:Bwear Curve Fc = Active
1 - 32000
10000
[Control
/Bkr
/Bwear]
Current2
Interrupted Current Level #2
Only available if:Bwear Curve Fc = Active
0.00 - 2000.00kA
1.00kA
[Control
/Bkr
/Bwear]
www.eaton.com
386