CCE-3000 Series 

Installation Guide

Installation Guide

Pneumatic-Electric Relays, Single and Multi-Stage

CCE-3000 Series

 

 

 

Mounting

The CCE-3000 Series relays are 

not

 position sensitive 

and may be mounted in any orientation.

Model CCE-3001

1.  Surface mount using the two 3/16" diameter 

holes.

2.  Bulkhead mount using the 9/16-18 boss and nut.

Model CCE-3002/3003

1.  Surface mount using the two 3/16" diameter 

holes.

2.  Bulkhead mount using two #6 self-threading 

screws.

Mounting 

1

Model CCE-3001 

1

Model CCE-3002/3003  1

Connections and Wiring  1

Electrical 

1

Air Supply 

1

Adjustments and Calibration  2
Accessories 

2

Maintenance 

2

Specifications  2
Important Notices  2

CCE-3001

CCE-3003

Connections and Wiring

Electrical

Connections are made to 1/4" quick connect ter-

minals. Do not exceed the electrical ratings of the 

switches (see 

Specifications on page 2

).

1.  Connect to the Common “C” and Normally Open 

“NO” terminals if a fall in signal should break the 

circuit.

2.  Connect to the Common “C” and Normally 

Closed “NC” terminal if a fall in signal should 

make a circuit.

Air Supply

1.  Using 1/4" (6 mm) OD polyethylene tubing, 

connect the signal to the 3/16" (5 mm) inlet in the 

bottom of the unit.

2.  Limit the signal to 30 psig (207 kPa) max.

 CAUTION

Pneumatic devices must be supplied with clean, dry 
control air. Any other medium (e.g., oil or moisture 
contamination) will cause the device to fail.