CCE-3000 Series
2
Installation Guide
Adjustments and Calibration
1. Choose a setpoint between 2 and 20 psi (14 and
138 kPa).
NOTE:
The differential on these models is 1 psi
minimum and 2 psi maximum (7 and 14
kPa).
2. Turn the setpoint adjustment wheel until the
bottom
of the wheel lines up with the signal
pressure listed beside the spring.
3. Repeat for each switch.
NOTE:
A gauge may be installed before completing
Step 2 to calibrate the relay to a particular
signal pressure.
© 2012 KMC Controls, Inc.
155-019-01E
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com
Important Notices
The material in this document is for information
purposes only.
The contents and the product it
describes are subject to change without notice.
KMC Controls, Inc. makes no representations or
warranties with respect to this document. In no event
shall KMC Controls, Inc. be liable for any damages,
direct or incidental, arising out of or related to the
use of this document.
Accessories
ICI-1005
Pressure gauge
Setpoint Range
2 to 20 psi (14 to 138 kPa)
Differential
Fixed differential, 1 to 2 psi
nominal (7 to 14 kPa)
Pressure Max.
30 psi (207 kPa)
Connections
Air
3/16" (5 mm) nipples for 1/4" (6
mm) O.D. polyethylene
tubing
Electrical
1/4" quick-connect terminals
Switching Action
SPDT each stage
Electrical Ratings
25 amps each switch (non-
inductive) @ 120/240/277 VAC,
1 HP @ 125 VAC, 2 HP @ 250
VAC, 750 VA pilot duty
Weight
CCE-3001
2 oz. (57 grams)
CCE-3002
4.5 oz. (128 grams)
CCE-3003
5 oz. (142 grams)
Material
Housing
Black polycarbonate
Diaphragm
Silicone
Temperature Limits
Operating
40 to 150° F (4 to 60° C)
Shipping
–40 to 150° F (–40 to 60° C)
Approvals
UL recognized
Patent Number 4,855,545 (CEE-3002/3003)
Specifications
Maintenance
No routine maintenance is required. Careful instal-
lation will help ensure dependable, long-term reli-
ability and performance.