Distributed busbar protection REB500

Product Guide

Summary of Contents for Relion REB500

Page 1: ...Relion Distributed busbar protection REB500 Product Guide...

Page 2: ...Contents 1 Main features 4 2 Application 4 3 Mode of installation 9 4 System design 10 5 Functionality 12 6 Additional features 16 7 Requirements 16 8 REB500 Process bus configuration 18 9 Hardware de...

Page 3: ...by ABB ABB assumes no responsibility for any errors that may appear in this document Copyright 2016 ABB All rights reserved Trademarks ABB and Relion are registered trademarks of the ABB Group All oth...

Page 4: ...0 detects all phase and earth faults in solidly grounded and resistive grounded power systems and phase faults in ungrounded systems and systems with Petersen coils The main CTs supplying the currents...

Page 5: ...K 505 352 BEN Product version 8 2 Issued 2016 03 01 Revision ABB 5 BI1 QA1 QB1 QB2 QB3 BI1 QA1 QB1 QB2 QB3 QB1 QB2 QB3 QB2 QB1 QB3 QB1 QB2 QB3 BI1 QA1 QB1 QB2 QB3 BI1 QA1 QB1 QB2 QB3 BI1 QA1 Figure 3...

Page 6: ...CZ PDIF Current plausibility check Overcurrent protection definite time 51 OCDT PTOC Trip command redirection 94RD PSCH Software matrix for inputs outputs trip matrix Event recording up to 1000 events...

Page 7: ...rcurrent protection 51 OCDT PTOC Inverse time overcurrent protection 51 OCINV PTOC Directional overcurrent definite time protection 67 DIROCDT PTOC Directional overcurrent inverse time protection 67 D...

Page 8: ...sible Only one hardware version for Settable 1A and 5A rated current inputs Nominal frequencies of 50Hz and 60Hz Minimum number of spare parts needed due to standardization and low number of varying u...

Page 9: ...a central relay room Centralized installation The central processing unit and the bay units are mounted in 19 racks up to two bay units each rack according to the size of the busbar system in one or m...

Page 10: ...e three phase voltages and two busbar voltages to allow the recording of voltage disturbances see Chapter 10 After acquisition the analog current and voltage signals are converted to numerical signals...

Page 11: ...ting position Additional plug and play functionality Bay units can be added to an existing REB500 system in a simple way Due to the modular and flexible architecture of the software integration of new...

Page 12: ...central unit Phase comparison The second measuring principle determines the direction of energy flow and involves comparing the phases of the currents of all the feeders connected to a busbar section...

Page 13: ...ciated CTs a signal derived from the breaker position and the close command is applied The end fault protection is enabled a certain time after the circuit breaker has been opened In the event of a sh...

Page 14: ...sed within the busbar protection algorithm Note Stored disturbance data can be transferred via the central unit to other computer systems for evaluation Files are transferred in the COMTRADE format Co...

Page 15: ...stalled in the central unit and in the bay units comprises a graphical monochrome LCD with a resolution of 320x240 pixels each for displaying system data and error messages keys for entering and displ...

Page 16: ...inspection activities on the primary equipment respectively Redundant power supplies Optional The central unit may be ordered with a redundant power supply Time synchronization The absolute time accu...

Page 17: ...chemes The relatively low CT performance needed for the busbar protection makes it possible for it to share protection cores with other protection devices Current transformer requirements for stabilit...

Page 18: ...tributed busbar protection REB500 1MRK 505 352 BEN Product version 8 2 Issued 2016 03 01 Revision 18 ABB 8 REB500 Process bus configuration Figure 12 REB500 Process bus configurations up to 60 Bay Uni...

Page 19: ...ting kit 19 rack mounting kit See ordering for details about available mounting alternatives Layout and dimensions Bay Unit Flush mounted IED Figure 13 Flush mounted Bay Unit into a panel cutout A 240...

Page 20: ...ck mounted IEDs Figure 15 Two rack mounted Bay Units side by side A 224 mm 12 mm with ring lug B 25 5 mm C 482 6 mm 19 D 265 9 mm 6U E 13 mm Layout and dimensions Central Unit Rack mounted IED Figure...

Page 21: ...5 352 BEN Product version 8 2 Issued 2016 03 01 Revision ABB 21 10 Connection diagrams Rear view Bay Unit Rear view Central Unit X0 X1 X8 X304 X9 X415 X336 X339 X1000 X1008 X1009 X347 X349 X450 X331 X...

Page 22: ..._2 TRIP2 TRIP CB L1_2 Start BFP L2_2 TRIP2 Start BFP L3_2 TRIP CB L2_2 DC2 TRIP2 Start BFP L1L2L3_2 TRIP CB L3_2 Spare DC1 BFP remote trip Cannel1 Spare DC2 BFP remote trip Cannel2 X324 DC Spare Spare...

Page 23: ...Precision binary outputs X326 Option X326 Option DC TRIP1 Spare TRIP CB L1_1 DC TRIP1 Spare TRIP CB L2_1 DC TRIP1 Spare TRIP CB L3_1 TRIP2 TRIP CB L1_2 X329 Option TRIP2 DC TRIP CB L2_2 Spare TRIP2 D...

Page 24: ...input L2_0 Line Current input L3 Phase current L3 Current input L3_0 Line Current input N Neutral current L0 Current input N_0 Line Voltages X102 Option Voltage input L1 Phase voltage L1 Voltage inpu...

Page 25: ...Revision ABB 25 Interfaces X0 Connection to a detached HMI LHMI will be switch off if X0 is used X1 Connection to REB500 Process bus via Ethernet switch X4 not used X9 not used Power Supply X410 DC A...

Page 26: ...C Protection blocked Spare DC Output relays blocked Spare DC Spare Isolator alarm DC Switch inhibit Spare DC Spare Differential current alarm Spare DC Busbar protection tripped System Alarm DC DC Brea...

Page 27: ...re DC Accept bus image alarm External reset DC Block all protection functions Block output relays DC Block busbar protection Block breaker failure protection DC Spare Spare X334 Option 06 04 OC11 05 O...

Page 28: ...5 LAN1 100BaseFx LC Connection to REB500 process bus via Ethernet switch X1008 Synchronization input RS485_GNDC IRIG B RS485_RX TERM 01 02 03 RS485_RX RS485_RX RS485_TX 04 05 06 RS485_TX TERM RS485_TX...

Page 29: ...for which the equipment under specified conditions is able to perform its intended functions according to the specified requirements Inputs Outputs Power Supply Table 6 Analog inputs Description Valu...

Page 30: ...9 VDE 0435 Part 303 Table 8 Binary input Description Value Operating range Maximum input voltage 300 V DC Rated voltage 24 250 V DC Current drain 1 6 1 8 mA Power consumption input 0 38 W Threshold vo...

Page 31: ...Value Rated voltage 33 288 V DC Continuous contact carry 0 5 A DC DC make and carry ton 1 s single shot toff 600 s L R 10 ms USW 150 V 10 A DC DC make and carry ton 1 s single shot toff 600 s L R 10 m...

Page 32: ...port type ST for IEC 60870 5 103 serial Table 18 Optical serial port X1009 Wavelength Fiber type Connector Permitted path attenuation1 820 nm MM 62 5 125 m glass fiber core ST 6 8 dB approx 1700m leng...

Page 33: ...t value Reference Cold tests operation storage 96 h at 25 C 16 h at 40 C 96 h at 40 C IEC 60068 2 1 ANSI C37 90 2005 chapter 4 Dry heat tests operation storage 16 h at 70 C 96 h at 85 C IEC 60068 2 2...

Page 34: ...diated amplitude modulated 10 V emf f 150 kHz 80 MHz 20 V m rms f 80 1000 MHz and f 1 4 2 7 GHz IEC 60255 26 IEC 61000 4 6 level 3 IEC 60255 26 IEC 61000 4 3 level 3 ANSI C37 90 2 2004 Fast transient...

Page 35: ...0 5 30 MHz Radiated RF emission 30 230 MHz 230 1000 MHz 79 dB V quasi peak 66 dB V average 73 dB V quasi peak 60 dB V average 40 dB V m quasi peak measured at 10 m distance 47 dB V m quasi peak measur...

Page 36: ...5 21 1 Class 1 Vibration endurance test IEC 60255 21 1 Class 1 Shock response test IEC 60255 21 2 Class 1 Shock withstand test IEC 60255 21 2 Class 1 Bump test IEC 60255 21 2 Class 1 Seismic test IEC...

Page 37: ...Ik min for fN 50 60 Hz incl tripping relays CT ratio per feeder 50 to 10 000 1 A 50 to 10 000 5 A adjustable via HMI Reset time 40 to 100 ms at IDiff 1 Ik min for fN 50 60 Hz For details about pickup...

Page 38: ...the reclosure time The discrepancy factor is the maximum permissible difference between the amplitudes of two phases Table 31 Current release criterion 51 PTOC Function Parameter Range Value Accuracy...

Page 39: ...s Test events 100 1000 User activity events 2048 Table 35 Disturbance recorder RDRE Options analog channel fn Recording period Sample rate selectable 4 currents and 5 voltages 50 Hz 60 Hz 4000 Hz 4800...

Page 40: ...Language SCL GOOSE reception for use as BFP start signals IEC 60870 5 103 IEC 60870 5 103 supports Time synchronization typical accuracy 5 ms Optical connection 9600 or 19200 Bd Subset of binary even...

Page 41: ...uble cubicle 2400 x 800 x 2200 mm triple cubicle largest shipping unit Total weight with all units inserted approx 400 600 kg per cubicle Clearance between IEDs 2U vertical Terminals Terminal type Con...

Page 42: ...ination with other functions and that some functions require specific hardware selections Central Unit Order Code rules Software option multiple selection is possible LHMI language and LHMI additional...

Page 43: ...tem up to 50 BU S50 Protection system up to 60 BU S60 Communication No communication X0 IEC 61850 8 1 A1 IEC 60870 5 103 A2 LHMI first language English IEC German French B1 LHMI additional language No...

Page 44: ...Unit cont d Example REB500 8 2 CU04 S10 A1A2 B1X0 E K SA A F A A A C REB500 8 2 CU04 S B1X0 E F A A C Binary input output module No board in this slot X BIO01 9BI 9BO A A Communication and processing...

Page 45: ...C3 Pole discrepancy C4 Overcurrent release C5 Neutral current measurement for busbar protection C6 Voltage protection Undervoltage release D1 Multipurpose protection Bay protection L V2 F2 LHMI first...

Page 46: ...mounting of LHMI incl Ethernet cable 2m B2 Detached mounting of LHMI incl Ethernet cable 3m B3 Detached mounting of LHMI incl Ethernet cable 4m B4 Detached mounting of LHMI incl Ethernet cable 5m B5 C...

Page 47: ...edundant power supply module BA 110 250 V DC 110 230 V AC no redundant power supply module CA 110 250 V DC 110 230 V AC redundant power supply module DA Remark All switches of the system shall be from...

Page 48: ...VD HMI500 Configurator ver 8 2 including user documentation LED label template 1MRK010011 AC Front connection cable between LCD HMI and PC 1MRK001665 CA LED Label special paper A4 1MRK002038 CA LED La...

Page 49: ......

Page 50: ...ABB AB Substation Automation Products SE 721 59 V ster s Sweden Telephone 46 0 21 32 50 00 Facsimile 46 0 21 14 69 18 http www abb com substationautomation 1MRK 505 352 BEN Copyright 2016 ABB All righ...