MesCom
– Workshop Manual – D6000/i14/V10
© Dycon Ltd 2014
-
49
7.5.4.6
UNSOL
Send events of this point to data collection servers.
9876 POINT Output1 UNSOL yes
9876 POINT Output1 UNSOL no
7.5.4.7
CALL
When an event occurs on this point trigger a call to the primary host.
The only primary host currently supported by the MesCom is an FTP server for HTML or
CSV file upload. See section 12 for more detail.
9876 POINT Output1 CALL yes
9876 POINT Output1 CALL no
7.5.5 Routine Notifications (data logging)
Using the POINT LOG, NLOG and OPTION LOGINT, SYNC parameters allow the MesCom
to be configured to create and send notifications on a periodic basis. This can be used as a
data logging function or a poll notification to indicate the MesCom is still functioning.
POINT LOG - sets which points to create routine events for.
POINT NLOG - if LOG is set for the point this causes the event to be notified to SMS contact
(Note: all users are sent the routine message).
OPTION LOGINT - sets the period between routine events.
OPTION SYNC - sets the time each to create a routine event synchronising the process over
multiple days (minutes past midnight).
9876 POINT Temperature LOG yes NLOG yes
9876 OPTION Output1 LOGINT 60 SYNC 600
Eg. Send a temperature reading every hour on the hour.
7.6 Assigning Signals to Points
Warning the feature if for advanced use only, incorrect use could disable the MesCom.
Signals can be re-mapped to any point, this is primarily for planned development of the
MesCom platform but can be used to monitor a signal input in multiple ways.
Eg. Analogue tank level with a timer input how long it is below a fixed point.
DEV parameter specifics the address of the
slave device from with to get the value for
the point.
DEV
definition
0
MesCom Build-in inputs
and outputs
1-254
Reserved for external
devices
255
Reference to defined
internal point