*Average is a moving average calculation based on the given number of samples.
InputValue = ((n-1) x oldInpu newReading) / n
See section 7.5 for more detail.
Please Note: the AVERAGE and DEBOUNCE keywords are interchangeable; a point will
either use the value as number of samples to average or number of samples to debounce
depending on the input type.
The LEVELS labels each have a maximum of 16 characters
– no spaces.
7.4.2 Digital Input
Bottom
Threshold
On
Off
Hysteresis
Input
V
a
lue
0v
3.0v
Of
f
On
Of
f
On
7.4.2.1
Schmitt Input / Dead Zone Input
On
Off
Hysteresis
Bottom
Threshold
Inpu
t
V
a
lue
0v
3.0v
Of
f
On
Input voltage reading is compared to the threshold to determine which state the input is in.
The reading state is then debounced and only once the debounce criteria* is met, does the
input state change.
The digital input requires one threshold but due to the universal nature of the MesCom point
system, all 4 thresholds need to be configured. The first threshold is used - the others are