ADDR parameter specifics the address of
the input or output point within the slave
device (see DEV above) from which to get
the value for the point.
See right for the address of the MesCom
build-in inputs and outputs (DEV = 0)
ADDR
DEV=0 definition
0,1,2
Reserved
3
Input 1
4
Input 2
5
Input 3
6
Input 4
7
Internal temperature
8
Supply voltage
9
Battery voltage
10
Radio module powered
11-63
Not defined
64
Test button
65-127
Not defined
128
Output 1
129
Output 2
130-191
Not defined
192
Radio registered
193
Signal strength
194
Reserved
195
Fault status
9876 POINT 6 DEV 0 ADDR 3
7.6.1 Internal Monitoring
Internal Temperature
Temperature of MesCom circuit board
Supply Voltage
Primary supply voltage
Battery Voltage
Battery voltage (charging voltage)
Radio Module powered
Digital: radio module on/off
Test Button
Digital: test button press/released
Radio Registered
Digital: registered on network or not
Signal Strength
GSM signal strength indicator
Fault status
Digital: MesCom in fault condition.
7.7 OPTION Command Parameters
7.7.1 IDENT
Name of device /
unit’s identifying name. This name will be prefixed to messages from the
MesCom to help identify the source of the message should the phone number change or not
be stored in the receiving phone.
Maximum of 24 characters with no spaces (we recommend you replace spaces with
underscore).
Factory default: MesCom
9876 OPTION IDENT <name_of_device>