MesCom
– Workshop Manual – D6000/i14/V10
© Dycon Ltd 2014
-
22
Passwords are case sensitive and although commands, keywords and labels are not case
sensitive, labels will be displayed in the case given when set.
The command format is <password> <command> <optional variables …>
If an incorrect password is sent or the command is not recognised, including commands
above
a user’s access level, the MesCom will not respond. The MesCom will NOT reply with
an error or fail response. A lack of response should be interpreted as a failure. This is to
avoid responding to messages from network operators and incorrect numbers.
7.1 Basic Configuration
7.1.1 General Configuration
MesCom settings you may wish to change are included below; see section 7.7 for a full list.
IDENT
The unit’s identifying name
a string (no spaces) of up-to 24
characters
PSAVE
The power saving
mode
0
– never enter power saving (least power saving)
1
– save power when battery is low
2
– save power when using battery
3
– save power whenever possible (most power saving)
WAKE
The time the MesCom keeps the radio
powered after an action occurs
Number of seconds (minimum 100s,
max 32767)
SLEEP
The maximum time the radio is
powered off between check for new text
messages
Number of minutes (minimum 5
minutes, max 32767)
LOGINT
The routine logging interval
Number of minutes (0 disables max
32767)
SYNC
The synchronisation time for routine
logging
Number of minutes past midnight (eg
300 = 5am 1440 >= disabled)
PULLUP Inputs are pulled up or down when the
signal is disconnected.
UP/DOWN YES/NO TRUE/FALSE
(Pull up for volt-free contacts)
Example:
9876 OPTION IDENT MyGarage PSAVE 2 WAKE 180 SLEEP 60
9876 OPTION LOGINT 180 SYNC 300 PULLUP YES
Please Note: All labels MUST contain NO spaces - we suggest underscore is used instead.