MesCom
– Workshop Manual – D6000/i14/V10
© Dycon Ltd 2014
-
48
9876 POINT Input2 READMIN 0.6 DISPMIN 12
9876 POINT Input2 READMAX 2.6 DISPMAX 42
9876 POINT Input2 PREFIX rh SUFFIX % UNLIM Shorted OVLIM OpenCircuit
ReadMin and ReadMax values are input voltage values in the range 0.0000 to 3.0000.
The PREFIX and SUFFIX labels each have a maximum of 8 characters
– no spaces.
The UNLIM and OVLIM labels each have a maximum of 12 characters
– no spaces.
7.5.4 Point Action Flags
All points have settings to determine what actions should be taken when a change is
detected.
7.5.4.1
ENABLE
Allow the points status to be processed; when not set the input is disabled and no actions
are taken should a change occur.
9876 POINT Output1 ENABLE yes
9876 POINT Output1 ENABLE no
7.5.4.2
ALARM
Alarm messages (SMS notifications) can be suppress by the OPTION MAXSKIP setting if a
point changed state multiple times without any other point changing state. This is highlight
the end state of a point and reduce unwanted SMS messages, The Default if to skip up to 8
events but this can be reduced to zero should the user wish to receive all events.
Create an event when the point changes state, you can select positive (restore)and negative
(fault)edges for digital inputs and outputs, for analogue input a restore is returning to
‘normal’
middle state and fault is moving away from it.
9876 POINT Output1 ALARM both
9876 POINT Output1 AlARM pos
9876 POINT Output1 AlARM neg
9876 POINT Output1 AlARM restore
9876 POINT Output1 AlARM fault
9876 POINT Output1 AlARM no
7.5.4.3
LOG
Create a routine log of point value, the interval of which is controlled by the OPTION
LOGINT command.
9876 POINT Output1 LOG yes
9876 POINT Output1 LOG no
7.5.4.4
NLOG
Send routine logs as an event notification to SMS users.
9876 POINT Output1 NLOG yes
9876 POINT Output1 NLOG no
7.5.4.5
SMS
Send events of this point to SMS users.
9876 POINT Output1 SMS yes
9876 POINT Output1 SMS no