MesCom
– Workshop Manual – D6000/i14/V10
© Dycon Ltd 2014
-
47
Full
High
Normal
Low
Empty
Hysteresis
Bottom
Threshold
Low
Threshold
High
Threshold
Top
Threshold
0v
3.0v
D
ec
re
as
ed to
E
m
pty
Inc
re
as
ed to
Low
Inc
re
as
ed to
N
orm
al
D
ec
re
as
ed to
Low
Point Value
Input Signal
Value is number of samples (minimum 0 maximum 32767).
We recommended you do not use a value less than 10.
9876 POINT Input1 DEBOUNCE 100
9876 POINT Input2 AVERAGE 100
The AVERAGE and DEBOUNCE parameters are stored as the same value in the MesCom,
this value being used as average for analogue inputs and debounce for all others.
7.5.3 Point Scaling
The displayed value of an input or output can be scaled to a real world value in the range
from -9999.9999 to +9999.9999 with prefix and suffix (8 characters). In addition there are 2
phrases for under range and over range (12 characters).
The scaling is configured by specifying 2 points between which the value is linearly
interpolated, outside which is interpreted as under or over range (12 characters).
Each point is specified by a displayed ‘real world’ value and a reading ‘electronic’ value.
Over
Range
Input Voltage
Input ADC count
65535
3.0v
0
0.0v
Under
Range
READMIN
READMAX
DISPMAX
DISPMIN
D
is
p
la
y
e
d
V
a
lu
e