7.7.21
HOLDOFF
Pause between event happening and notification being send to allow for additional events to
happen, therefore allowing for a more complete picture of the event to be sent and hopefully
reducing the number of notifications caused by transient events.
Value in seconds: minimum 0s, maximum 32767s (approximately 9 hours).
Factory default: 5 seconds
9876 OPTION HOLDOFF 10
7.7.22
SUPPRESS
Input that triggers enter/exit suppress “Engineer on site” mode.
See section 4.3 for more detail on
“Engineer on site”.
255 to disable
“Engineer on site” mode.
Factory default: 0 (test button)
9876 OPTION SUPPRESS 1
Also see SUPPTIME parameter.
In addition to entering suppress mode, an admin user can enable/disable this mode with the
START/STOP keywords.
9876 OPTION SUPPRESS START
The suppress input will still be functional and SUPPTIME will still be used to disable
suppress mode after the time has expired.
7.7.23
SUPPTIME
Maximum time before exiting suppress
“engineer on site” mode.
Value in seconds: minimum 0 (disables timeout), maximum 32767s (approximately 9 hours).
Factory default: 3600 seconds (1 hour)
9876 OPTION SUPPTIME 600
Also see SUPPTIME parameter.