MesCom
– Workshop Manual – D6000/i14/V10
© Dycon Ltd 2014
-
53
7.7.11
MAXLEN
Maximum total call length. Disconnect a call if it has continued for a period of time.
Value in seconds: minimum 0s, maximum 32767s (approximately 9 hours).
Factory default: 600 seconds
9876 OPTION MAXLEN 600
7.7.12
SAMPLE
Input sampling period.
Value in milliseconds: minimum 20ms, maximum 65535ms (approximately 1 minute).
Factory default: 20 milliseconds
9876 OPTION SAMPLE 20
7.7.13
PULLUP
Input resistor. Inputs can be pulled up or pulled down. It is not possible to disable the input
resistor.
Options
Yes - Resistor pullup enabled (factory default).
No - Resistor pull down enabled.
9876 OPTION PULLUP NO
7.7.14
LOGINT
Routine logging interval. This can be used to trigger a periodic reading of an input (eg.
temperature) to allow users to see a trend in that signal. Inputs and outputs can be individual
configured to be included in the routine logging - see POINT LOG parameter.
Please note this can be used to generate a large number of events and should be used with
caution. We recommend SMS only be used with a long interval.
Value in minutes: minimum 1min, maximum 32767min (approximately 22 days).
Factory default: 60 minutes
9876 OPTION LOGINT 60
Also see POINT LOG and NLOG parameters for logging behaviour.
7.7.15
HEALTH
Routine call interval. This can be used to trigger a periodic call to a host, which could be
used to confirm the device is still operational.
Value in minutes: minimum 5min, maximum 32767min (approximately 22 days).
Factory default: 1440 minutes
9876 OPTION HEALTH 10080