7.5 Generic POINT Settings
7.5.1 Point Name
Each input and output can be given a name. (Maximum 24 characters
– no spaces)
No spaces - we recommend you use underscore.
9876 POINT Input1 PNAME TankLevel
9876 POINT TankLevel PNAME FuelLevel
Use the VIEW LIST command to see a list of current points.
7.5.2 Debounce and Averaging
Debounce is performed on digital inputs, including counters and timers.
The input signal must be in a constant state for the defined number of samples for the state
to change.
On
Off
Hysteresis
Bottom
Threshold
Input
S
igna
l
0v
3.0v
P
oi
nt
S
ta
te
Debounce
Debounce
Debounce
Of
f
On
On
Off
Average is performed on analogue inputs.
The input signal has a modified moving average applied to it.
New Value = old value x (samples-1) + new reading
samples