MesCom
– Workshop Manual – D6000/i14/V10
© Dycon Ltd 2014
-
54
7.7.16
SYNC
Time of day to synchronise activities. Allow routine logs and calls to be synchronised daily to
assist analysis or logged data, Ie. A log will be performed at this time.
Value in minutes past midnight: minimum 0, maximum 1440
zero = midnight, 1440 and above disable the synchronisation.
Factory default: 600 minutes past midnight (10:00am)
9876 OPTION SYNC 600
7.7.17
CKINT
How often to update the clock. The MesCom has a RTC but this can be periodically
synchronised with an external clock.
Value in minutes: minimum 0min (disabled), maximum 32767min (approximately 22 days).
Factory default: 60 minutes
9876 OPTION LOGINT 60
Also see CKSRC and TIME parameters for more control of MesCom clock.
7.7.18
CKSRC
Source for clock to synchronise with.
Options
0
– Manual update only, disable automatic synchronisation of clock.
1
– Use any available clock source (see below) (factory default).
2
– GSM clock directly from network or from received SMS header.
3
– Will be provided by or fetched from host on next connection.
9876 OPTION CKSRC 1
Also see CKINT and TIME parameters for more control of MesCom clock.
7.7.19
BAUD
Terminal interface.
Permitted values are; 300, 600, 1200, 4800, 9600, 19200bps.
Any other value will cause the MesCom to default to 9600bps.
Factory default: 19200bps
9876 OPTION BAUD 9600
7.7.20
XOFF
Maximum period to be in software flow control hold state before resuming (XON character
assumed missing).
Value in milliseconds: minimum 1000ms, maximum 32767ms (approximately 0.5 minute).
Setting to a value of 0 will disable automatic resume (not recommended).
Factory default: 10000 milliseconds
9876 OPTION REGINT 10000