MesCom
– Workshop Manual – D6000/i14/V10
© Dycon Ltd 2014
-
51
7.7.2 PSAVE
Power saving mode, when the radio module should be powered down to save power. In
power saving mode the inputs will continue to be monitored and should a notification need to
be sent, the radio module will be powered. Additionally the radio module will be periodically
powered to check for incoming messages. Power saving mode will only be (re)entered after
all messages have been processed. When the radio module is powered down, messages
can’t be receive so commands and output controls will not be performed promptly.
Options
0
– Never enter power saving mode / always keep radio module on.
1
– Only switch radio module off when no primary supply and battery is low.
2
– Switch radio module off when there is no primary supply (factory default).
3
– Keep radio module off as much as possible (lowest power consumption).
9876 OPTION PSAVE 2
Also see WAKE and SLEEP parameters for power saving behaviour.
7.7.3 WAKE
Amount of time to delay (re)entering power saving mode after a notification has been sent or
a command has been processed. Additionally this sets the initial delay after loss of primary
supply before entering power saving mode and the period of time to stay powered for when
periodically checking for incoming messages.
Value in seconds: minimum 100s, maximum 32767s (approximately 9 hours).
Factory default: 120 seconds
9876 OPTION WAKE 120
7.7.4 SLEEP
Interval for periodic powering of radio module in power saving mode.
While in power saving mode with the radio module switch off the MesCom can’t receive SMS
command message this. This setting allows the radio module to be switch so that the
MesCom and check if any SMS messages are pending and action them. Value in minutes:
minimum 5 min, maximum 32767 min (approximately 22 days).
Factory default: 360 minutes
9876 OPTION SLEEP 180
7.7.5 REBOOT
Radio Module reboot period. Some mobile networks are based against fixed installations
and may force a radio device that has been powered and not changed cell to disconnect
from the network, to avoid this the MesCom can be configured to switch the Radio module
off and back on if powered to a number of hours.
Value in hours minimum 0(disabled) maximum 32767hours (approximately 3 years).
Factory default: 72 hours
9876 OPTION REBOOT 72