80
ED900
02-2020
08125330
dormakaba ED900 Installation Instructions – Double egress door
Chapter 24
Step 1
Press
Press and hold PRG > 3 s to enter
program mode, AS parameter
displayed.
Step 2
Press
Scroll to
dL
parameter.
Step 3
Press
Displays "00" , factory setting.
Step 4
Press
"00" starts flashing.
24.2.3 Inactive door, set parameter dL.
1. Set program switch to CLOSE.
2. Set parameter dL (door type) for inactive door.
Step 5
Press
Scroll to select parameter value
("3" as an example).
Step 6
Press
Saves value entered. Display stops
flashing.
Step 7
Press
Returns to door type parameter.
Step 25
Press
Exits program mode. Operator is ready
for operation.
24.3 Connect communication cable between operators
Fig. 24.3.1 Double door operators, communication cable
1
RJ45 jack
(horizontal) for
communication
cable
2
Communication
cable
2
Communication
cable 08125243
Fig. 24.3.3 Communication cable
24.3.1 Install communication cable.
1. Set program switch to CLOSE.
2. Connect communication cable to active
and inactive operator RJ45 jacks.
3. Secure cable to header
23.3.2 Test door operation
1. Set program switch to AUTO.
2. Test double door operation.
• Use knowing act device
Fig. 24.3.4 Program switch
1
Program switch,
3 position
1
1
4
Fig. 24.3.2 RJ45 jack
1
RJ45 jack
4
Program switch
cable
1
1
2
2