dormakaba ED900 Installation Instructions – Double egress door
Appendix A
Parameter
Value
range
Units
Factory
setting Description
Unlocking during business hours
26
0 - 1
0
0
Door is always locked when it reaches closed position.
1
1. In automatic mode, door will not lock when it reaches closed position. This
achieves faster door opening when system is equipped with motor driven locks.
2. If an electric strike opener is used, it must be suitable for 100% continuous duty
factor to avoid possibility of damage.
Status relay function, X7 terminals
0
Status relay is deactivated.
27
0 - 6
1
1
Status relay activated as soon as door reaches door "closed" position.
2
Status relay activated as soon as door reaches door "open" position.
3
Status relay activated when error codes are displayed on 2 digit operator display.
4
"Door closed and locked" activates status relay.
5
Status relay activated when information or error codes are displayed on 2 digit
operator display.
6
1. Status relay activated when door is opened further than opening angle
parameter
OA
, set during learning cycle.
2. Parameter
OA
value can only be changed using dormakaba handheld or by
performing another learning cycle.
Locking device output configuration;
output X3, 1G (24V) and input X6, 4/4a
Reference Chapter 7
28
0 - 1
0
0
Locking device output terminal X3, 1G (24V) is independent of Input X6, 4/4a.
1
1. Locking device output terminal X3, 1G (24V) is turned on as soon as contact at
X6, 4/4a is opened..
2. Terminal X3, 1G 24V output is on for as long as contact at X6, 4/4a is open,
motor lock with a 100% duty factor is required.
3. This function is not available for DCW motor locks.
Cycle counter
1. Total number of opening and closing cycles displayed is shown in increments of 10000.
• Display value, "4", 40,000 cycles.
• Display value, "53", 530,000 cycles.
2. Total number of cycles can be displayed on dormakaba handheld.
3. A display value of "99" means 990,000 cycles or greater.
29
0 - 99
* 10000
cycles
Delete error log
30
0 - 1
0
0
No function.
1
1. When "1" entered, Error log is deleted.
2. Parameter is then automatically reset to "0".
A.1.1 Driving parameters detail.