Error Response
If the first register in this write command is not in the valid range of registers, the PowerScout returns an
error message.
Report Slave ID
This command is used to read the description, the current status and other information specific to a
remote device. A normal response includes the data contents specific to the device.
Command Information
Command
Layout
Example
Command
PowerScout address
nn
37
Command number
11
11
Table D-8: Format for Modbus Command 11 (17 in decimal)
Example Command
Example Request
Field Name
Command
(Hex)
Response
Field Name
Response
(Hex)
PowerScout address
37
PowerScout address
37
Command number
11
Command number
11
CRC low order bits
D7
Byte count
CRC high order bits
8C
Slave ID
Run indicator status
Additional data
Table D-9: Format for Modbus Command 11 (17 in decimal)
Slave ID
The PowerScout uses the following default format for the slave ID:
00hFFhDENT Instruments PowerScout 3, Serial Number, FW Rev Major Revision. Minor Revision, Scalar X
00hFFhDENT Instruments PowerScout 24, Serial number, FW Rev Major Revision. Minor Revision, Scalar {x}
Example:
00hFFhDENT Instruments PowerScout 3, PS3912001, FW Rev 1.0, Scalar 3
00hFFh DENT Instruments PowerScout 24, PS24712001, FW Rev 1.5, Scalar 3
The 00h is used for version control and the FFh indicates the meter is active. The 00h and FFh are two
bytes in front of the string that are not displayed on the RTU.
NOTE:
See
VERIS H8035/H8036 Emulation
for slave ID structure while in Veris emulation.