Modbus
Offset
Register
Description
45310
(PS24 only)
5309
Digital Port 1 Configuration
Turns pulses on/off
0 = No pulses, Port may be used as an on/off—
open/closed switch
44001 = System kWh pulses
44008 = System kVARh pulses
44011 = System kVAh pulses
45311
(PS24 only)
5310
Port 1 pulse output relay type
0 = normally open (HIGH)
1 = normally closed (LOW)
A
BSOLUTE
/N
ET
V
ALUE
M
EASUREMENT
R
EGISTERS
Offset refers to a base of 40001.
Modbus
Offset
Register
Description
* System=sum of three phases
44001
4000
kWh System LSW
System Total True Energy LSW (kWh)
44002
4001
kWh System MSW
System Total True Energy MSW (kWh)
44003
4002
kW System
System Total True Power (kW). Unsigned absolute
(ABS) value of ABS (kW L1) + ABS (kW L2) + ABS (kW
L3)
44004
4003
kW Demand System Max
System Maximum Demand (peak demand).
44005
4004
kW Demand System Now
Average Power (kW) for most recent demand window
44006
4005
kW System Max
System Maximum Instantaneous kW
(Highest kW sample measured)
44007
4006
kW System Min
System Minimum Instantaneous kW
(Lowest kW sample measured)
44008
4007
kVARh System LSW
System Total Reactive Energy LSW (kVARh)
44009
4008
kVARh System MSW
System Total Reactive Energy MSW (kVARh)
44010
4009
kVAR System
System Total Reactive Power (kVAR). Unsigned
absolute (ABS) value of ABS (kVAR L1) + ABS (kVAR L2)
+ ABS (kVAR L3)
44011
4010
kVAh System LSW
System Total Apparent Energy LSW (kVAh)
44012
4011
kVAh System MSW
System Total Apparent Energy MSW (kVAh)
69