Object
Identifier
Name
Description
12011
CT1 Value
CT1 Value
12012
CT2 Value
CT2 Value
12013
CT3 Value
CT3 Value
12030
CT Pulse Scalar
Changes the scaling of the output pulses
12040
Demand Window
Demand window size in minutes; default is 15 min
12050
Volts Multiplier
Multiply volts values by this scalar. For use with stepdown
transformer. Affects all parameters that use volts.
12061
CT1 Amps Multiplier
Multiply CT1 amps values by this scalar. For use with stepdown
transformer. Affects all parameters that use amps.
12062
CT2 Amps Multiplier
Multiply CT2 amps values by this scalar. For use with stepdown
transformer. Affects all parameters that use amps.
12063
CT3 Amps Multiplier
Multiply CT3 amps values by this scalar. For use with stepdown
transformer. Affects all parameters that use amps.
12070
Com Settings
Baud: 900=9600, 1900=19200, 3800=38400, 5700=57600,
7600=76800, 11500=115200
Parity: Add 00 = NO, Add 10 = ODD, Add 20 = EVEN
Stop bit: Add 0 = 1 (UART does not permit 0 stop bits), Add 1 = 1, Add
2 = 2
E.g., 901 = 9600 baud, no parity, 1 stop bit
12080
Service Type
A value of 1 configures the meter for Delta.
A value of 0 configures the meter for Wye.
A value of 2 configures the meter for Single Phase (PS24 only).
12090
Line Frequency
Line frequency setting for metering. 50 = 50 Hz, 60 = 60 Hz
12130
(PS3 Only)
CT Type All
Writes same type for all CTs: 1=MilliVolt, 2=Rogowski
12131
CT1 Type
1=MilliVolt, 2=Rogowski
12132
CT2 Type
1=MilliVolt, 2=Rogowski
12133
CT3 Type
1=MilliVolt, 2=Rogowski
87
Shop for Dent products online at:
1.877.766.5412
www.
PowerMeterStore
.com