Object
Identifier
Name
Description
13110
(PS3 only)
Port 1 pulse output relay type
0 = normally open (HIGH)
1 = normally closed (LOW)
13150
(PS3 only)
Digital Port 2 Configuration
Turns pulses on/off
0 = No pulses, Port may be used as an on/off—
open/closed switch
44001 = System kWh pulses
44008 = System kVARh pulses
44011 = System kVAh pulses
13160
(PS3 only)
Port 2 pulse output relay type
0 = normally open (HIGH)
1 = normally closed (LOW)
15000
(PS24 only)
Digital Port 1 Configuration
Turns pulses on/off
0 = No pulses, Port may be used as an on/off—
open/closed switch
44001 = System kWh pulses
44008 = System kVARh pulses
44011 = System kVAh pulses
15010
(PS24 only)
Port 1 pulse output relay type
0 = normally open (HIGH)
1 = normally closed (LOW)
A
BSOLUTE
/N
ET
V
ALUE
M
EASUREMENT
O
BJECTS
System=sum of three phases.
Object
Identifier
Name
Description
* System=sum of three phases
1000
kW Demand System Maximum
System Maximum Demand (peak demand) (Unsigned/Absolute)
1010
kW Demand System Now
Average Power (kW) for most recent demand window
(Unsigned/Absolute)
1020
kW Demand System Minimum
Min Average power window (kW) (Unsigned/Absolute)
1030
kW System
System True Power (kW). Unsigned absolute (ABS) value of
ABS (kW L1) + ABS (kW L2) + ABS (kW L3)
1031
kW System Net
System Power (kW) Signed net value of (kW L1) + (kW L2) + (kW L3)
1060
kW System Average
Equals kWh System / (Time Since Reset /3600 seconds/Hr)
(resettable)
1100
kW System Maximum
System Highest Instantaneous Draw Since Reset (kW)
1130
kW System Minimum
System Lowest Instantaneous Draw Since Reset (kW, resettable)