Modbus
Offset
Register
Description
* System=sum of three phases
44013
4012
kVA System
System Total Apparent Power (kVA). Unsigned WYE =
(kVA L1) + (kVA L2) + (kVA L3) Delta = SQRT (kW
system ^2 + kVAR system ^2)
44014
4013
Displacement PF System
System Displacement Power Factor (PF). Register is
100x actual value.
44015
4014
Apparent PF System
System Apparent Power Factor (PF). Register is 100x
actual value.
44016
4015
Amps System Avg
Average of all phases.
44017
4016
Volts Line to Line Avg
Voltage Line to line (Volts) Average.
44018
4017
Volts Line to Neutral Avg
Voltage Line to neutral (volts) Average.
44019
4018
Volts L1 to L2
Individual Phase to Phase Voltages
44020
4019
Volts L2 to L3
“
44021
4020
Volts L1 to L3
“
44022
4021
Line Frequency
Line Frequency (Hz)
44023
4022
kWh L1 LSW
Individual Phase True Energy LSW (kWh)
44024
4023
kWh L1 MSW
Individual Phase True Energy MSW (kWh)
44025
4024
kWh L2 LSW
“
44026
4025
kWh L2 MSW
“
44027
4026
kWh L3 LSW
“
44028
4027
kWh L3 MSW
“
44029
4028
kW L1
Individual Phase True Powers (kW)
44030
4029
kW L2
“
44031
4030
kW L3
“
44032
4031
kVARh L1 LSW
Individual Phase Reactive Energy LSW (kVARh)
44033
4032
kVARh L1 MSW
Individual Phase Reactive Energy MSW (kVARh)
70