Modbus
Offset
Register
Description
44607
4606
Service Type
A value of 0x0001 configures the meter for DELTA
A value of 0x0000 configures the meter for WYE
A value of 0x0002 configures the meter for Single
Phase (PS24 only)
44609
4608
Set Line Frequency
Line frequency setting for metering: 50=50 Hz,
60=60Hz
44612
4611
Communications Settings
Write 1833 to change to BACnet mode
50100
10099
CT1 Integer
Integer part of CT1
50101
10100
CT1 Decimal
Fractional part of NV_CT1
50104
(PS24 only)
10103
CT1 Voltage Source
Voltage source = Select voltage phase to associate
with CT for power and energy calculations. 0= not
used,1=L1, 2=L2, 3=L3,4=L1-L2,5=L3-L2, 6=L1-L3,
default=L1. Note this register is only active if Service
Type (44607) is set to 2 (Single/Independent)
50105
(PS24 only)
10104
CT1 Amps Multiplier
Amps multiplier= Multiply amps value by this scalar.
For use with 5A CTs and single leg monitoring of a
three phase load. Affects all parameters that use
amps (e.g., kW). Whole numbers only.
50125
10124
CT1 Type
Select 1=mV or 2=Rogowski CT1s
50199
10198
CT1 Phase Shift
Phase Shift X 100 +/-
50200
10199
CT2 Integer
Integer part of CT2
50201
10200
CT2 Decimal
Fractional part of NV_CT2
50204
(PS24 only)
10203
CT2 Voltage Source
Voltage source = Select voltage phase to associate
with CT for power and energy calculations. 0= not
used,1=L1, 2=L2, 3=L3,4=L1-L2,5=L3-L2, 6=L1-L3,
default=L1. Note this register is only active if Service
Type (44607) is set to 2 (Single/Independent)
50205
(PS24 only)
10204
CT2 Amps Multiplier
Amps multiplier= Multiply amps value by this scalar.
For use with 5A CTs and single leg monitoring of a
three phase load. Affects all parameters that use
amps (e.g., kW). Whole numbers only.
50225
10224
CT2 Type
Select 1=mV or 2=Rogowski CT2s
50299
10298
CT2 Phase Shift
Phase Shift X 100 +/-
50300
10299
CT3 Integer
Integer part of CT3
50301
10300
CT3 Decimal
Fractional part of NV_CT3
66