BACnet Output Port Objects
Refer to the following two tables to configure the PowerScout output ports when using the BACnet
protocol. Remember to add the correct increment of 20000 to the base object number that designates
each element on the PS24. See
Addressing an Element
.
PS 3
Object
Identifier
PS24
Object
Identifier
Name
Detailed Description
13020
NA
Port 1 output control when used as an
on/off—open/closed switch
0 = output LOW (closed) 1 = output HIGH
(open) [default]
Object 13100 present value must = 0 to use
13100
15000
Digital Port 1 Configuration
Turns pulses on/off
0 = No pulses, Port may be used as an
on/off—
open/closed switch
44001 = System kWh pulses
44008 = System kVARh pulses
44011 = System kVAh pulses
13110
15010
Port 1 pulse output relay type
0 = normally open (HIGH)
1 = normally closed (LOW)
Table F-4: BACnet Digital Port 1 Pulse Output
PS3
Object
Identifier
Name
Detailed Description
13030
Port 2 output control when used
as an on/off—open/closed switch
0 = output LOW (closed)
1 = output HIGH (open) [default]
Object 13150 present value must = 0 to use
13150
Digital Port 2 Configuration
Turns pulses on/off
0 = No pulses, Port may be used as an on/off—
open/closed switch
44001 = System kWh pulses
44008 = System kVARh pulses
44011 = System kVAh pulses
13160
Port 2 pulse output relay type
0 = normally open (HIGH)
1 = normally closed (LOW)
Table F-5: PS3 BACnet Digital Port 2 Pulse Output
96