Object
Identifier
Name
Description
* System=sum of three phases
9150
Apparent PF L1
Individual Phase apparent Power Factors (PF)
9180
Apparent PF L2
“
9210
Apparent PF L3
“
10000
Measured Line Frequency
Line Frequency (Hz)
10010
Time Since Reset
Seconds since accumulator registers were reset.
P
OSITIVE
P
OWER
/E
NERGY
M
EASUREMENT
O
BJECTS
Object
Identifier
Name
Description
* System=sum of three phases
1080
kW System Average Positive
Equals kWh System Positive / (Time Since Reset /3600 seconds/Hr)
(resettable) (Signed Net)
1110
kW System Maximum Positive
System Highest Instantaneous Positive Draw Since Reset (kW)
(Signed Net)
1140
kW System Minimum Positive
System Lowest Instantaneous Positive Draw Since Reset (kW,
resettable)
2010
kWh System Total Positive
System True Energy (kWh) Positive (Signed Net)
2040
kWh L1 Positive
Individual Phase True Energy (kWh) (Signed)
2070
kWh L2 Positive
“
2100
kWh L3 Positive
“
6010
kVARh System
System Total Reactive Energy (Signed Net)
6020
kVARh System Total Positive
System True Energy (kVARh) Positive (Signed Net)
6050
kVARh L1 Positive
Individual Phase Reactive Energy (kVAR) (Signed)
6080
kVARh L2 Positive
“
6110
kVARh L3 Positive
“
7001
kVAh System Total Positive
System Total Positive Apparent Energy (kVAh) (Signed Net)
Accumulates only when kW is positive
7020
kVAh L1 Positive
Individual Phase Apparent Energy (kVAh) (Signed)
7050
kVAh L2 Positive
“
7080
kVAh L3 Positive
“
92
Shop for Dent products online at:
1.877.766.5412
www.
PowerMeterStore
.com