Modbus
Offset
Register
Description
44069
4068
Firmware Major Revision
Major Revision Level (big software releases)
44070
4069
Firmware Minor Revision
Minor Revision Level (small software changes)
C
ONFIGURATION
R
EGISTERS
Modbus
Offset
Register
Description
40129
0128
Synchronize Register
Multiple PowerScout’s synchronization register
44066
4065
Clear Accumulated
Measurements
Writing 1234 resets all 'H' registers, accumulated
PowerScout data (kWh, kWh, etc) stored in flash to
CAM Default value
44525
(PS3 Only)
4524
CT Type All
Writes same type for all CTs: 1=MilliVolt, 2=Rogowski
44526
4525
Slave ID
!1=DENT, 1=Veris; Sets SLAVE_ID to Veris or DENT
44599
(PS3 only)
4598
CT Phase Shift All
CT Phase Shift X 100 +/-
Writes same value to Registers 50199, 50299, &
50399
44600
(PS3 only)
4599
CT Integer All
Integer value of all CTs, Writes same value to
Registers 50100, 50200, & 50300
44601
(PS3 only)
4600
CT Decimal All
Decimal value of all CTs, Writes same value to
Registers 50100, 50200, & 50300
44602
4601
Data Scalar
A Value of 0-6 that changes the scaling of certain
registers
44603
4602
Demand Window Size
Demand window size in minutes; default is 15 min
44604
4603
Volts Multiplier
Multiply volts values by this scalar. Use with Step-
down Transformer. Affects all parameters that use
volts (i.e., kW)
44605
(PS3 only)
4604
Amps Multiplier
Multiply amps value by this scalar. For use with x:5A
CTs and single let monitoring of a three phase load.
Affects all parameters that use amps (i.e, kW)
44606
4605
Communication Setting
Baud: 900=9600, 1900=19200, 3800=38400,
5700=57600, 7600 =76800, 11500=115200
Parity: Add 00 = NO, Add 10 = ODD, Add 20 = EVEN
Stop bit: Add 0 = 1 (UART does not permit 0 stop bits),
Add 1 = 1, Add 2 = 2
E.g., 901 = 9600 baud, no parity, 1 stop bit
65